§ 145.10. Location, number, and installation of fire extinguishers.

318 words·~1 min read·/us/cfr/t33/s§ 145.10·

A research copy — for the controlling text, always check the official state or federal source. Not legal advice.

(a)Approved portable and semi-portable extinguishers must be installed in accordance with Table 145.10(a).
(b)Semi-portable extinguishers must be located in the open so as to be readily seen.
(c)Semi-portable extinguishers must be fitted with a suitable hose and nozzle, or other practicable means, so all of the space can be protected.
(d)Table 145.10(a) of this section indicates the minimum number and size of fire extinguishers required for each space listed. Extinguishers with larger numerical ratings or multiple letter designations may be used if the extinguishers meet the requirements of the table. ::: {.table_head} Table 145.10(a)---Portable and Semi-Portable Extinguishers ::: Space Minimum required rating Quantity and location Safety Areas: Communicating corridors 2-A 1 in each main corridor not more than 150 ft apart. (May be located in stairways.) Radio room 20-B:C 1 in the vicinity of the exit. Accommodations: Sleeping accommodations 2-A 1 in each sleeping accommodation space outfitted for 4 or more persons. Service Spaces: Galleys 40-B:C 1 for each 2,500 sq ft of floor space or fraction thereof. Storerooms 2-A 1 for each 2,500 sq ft of floor space or fraction thereof. The extinguisher must be located in the vicinity of the exits, either inside or outside of spaces. Machinery Spaces: Gas-fired boilers 40-B 2 required. 160-B 1 required. 1 Oil-fired boilers 40-B 2 required. 160-B 2 required. 1 Internal combustion or gas turbine engines 40-B 1 for each engine. 2 Electric motors or generators of open type 40-B:C 1 for each 2 motors or generators. 3 ::: {.table_foot} 1 Not required where a fixed extinguishing system is installed. 2 When the installation is on the weather deck or open to the atmosphere at all times, then one 40-B extinguisher for every three engines is allowable. 3 Small electrical appliances, such as fans, are exempt. ::: \[CGFR 56-4, 21 FR 903, Feb. 9, 1956, as amended by USCG-2012-0196, 81 FR 48243, July 22, 2016\]
Connections1 cite this
Citation graph
cites case law
§ 145.10
Location, number, and installation of fire extinguishers.
Fed. Reg.×1
Cites 0Cited by 1 across 1 source
★   the supreme law of the land   ★
Don't Tread on Me
E Pluribus Unum — out of many, one

"If you don't know your rights, you don't have any."

Marginalia · a citizen's law index
A research desk, not legal advice. Always read the cited source before relying on a summary.
Questions or an issue? support@self-law.org
disclaimerMarginalia is a research index, not a law firm. Nothing on this site is legal, tax, or financial advice and no attorney–client relationship is formed by using it. Statutes, regulations, and case law change; summaries, search results, AI output, and member posts may be incomplete, out of date, or wrong. Any interpretation drawn from material on this site should be validated by a licensed attorney in your jurisdiction before you act on it.